Command Group: Calibration | Access: | Network interfaces: | |
TAC protected | RW | CANopen | |
| | MODbus | |
OF - Set Output Format | | PROFIbus | |
Synopsis: |
| Command | Response |
Get | OF | F<Value> |
Set | OF <Value> | OK (or ERR) |
|
Valid for | Min. value | Max. value |
141.181 |
0 |
3 |
141.184 |
0 |
3 |
141.185 |
0 |
3 |
141.186 |
0 |
3 |
142.181 |
0 |
3 |
142.184 |
0 |
3 |
142.185 |
0 |
3 |
142.186 |
0 |
3 |
143.181 |
0 |
3 |
143.184 |
0 |
3 |
143.185 |
0 |
3 |
151.181 |
0 |
3 |
151.184 |
0 |
3 |
151.186 |
0 |
3 |
152.181 |
0 |
3 |
152.184 |
0 |
3 |
162.181 |
0 |
3 |
179.181 |
0 |
3 |
181.181 |
0 |
3 |
64.181 |
0 |
3 |
64.184 |
0 |
3 |
69.181 |
0 |
3 |
78.183 |
0 |
3 |
|
OF Controls the Output format for
GG,
GN,
GL and
GW.
These formats supports multi range applications.
The values 0..3 selects a format to be used:
- 0 = No range indication and no decimal point in GL and GW answers.
- 1 = With range indication and no decimal point in GL and GW answers.
- 2 = No range indication and with decimal point in GL and GW answers.
- 3 = With range indication and with decimal point in GL and GW answers.
Overview of the formats:
|
GG |
GN |
GL |
GW |
0 |
G+01.100 |
N+01.100 |
L+00100+01100010F |
W+00100+01100010F |
1 |
G1+01.100 |
N1+01.100 |
L1+00100+01100010F |
W1+00100+01100010F |
2 |
G+01.100 |
N+01.100 |
L+00.100+01.100010F |
W+00.100+01.100010F |
3 |
G1+01.100 |
N1+01.100 |
L1+00.100+01.100010F |
W1+00.100+01.100010F |
Note that indicated decimal points are shown as DP = 3.
See also
MR,
CM1,
CM2,
CM3,
DP,
GN,
GT.
GS,
GL,
GW.